Categories
Our protection module for Water and Waste Water Products provides protection and monitoring of pumps and submersible mixers by all-in-one device for motor temperature measurement, bearing temperature measurement, leakage measurement, vibration measurement and voltage measurement.
Why our monitoring and protection unit?
Easy to install in control cabinet on top hat rail; quick and easy wiring with push-in terminals
Straightforward commissioning as each variant is pre-parameterised for the product it will be used with
Increased operating reliability due to warning and cut-out in the event of a fault, with warning option via general alarm contact
Extended service life of pumps and submersible mixers by preventive maintenance information
Simple analysis of diagnosis data with saved history, recorded operating data and trends as well as a fault history
Optimal condition monitoringof the pump, the pump system or the submersible mixer
Power Supply:
AC/DC 50/60Hz 24V
AC 50/60Hz 100-240V
Generally we provide four models for continuous monitoring and protection of pumps and mixers.
BASIC | STANDARD | EXTENDED | PREMIUM |
Main differences between each model are:
BASIC | STANDARD | EXTENDED | PREMIUM | |
Motor temperature | PTC, PT100,PT1000, Bimetal | PTC, PT100,PT1000, Bimetal | PTC, PT100,PT1000, Bimetal | PTC, PT100,PT1000, Bimetal |
Temperature 1 | PTC, PT100,PT1000, Bimetal | PTC, PT100,PT1000 | PTC, PT100,PT1000 | PTC, PT100,PT1000 |
Temperature 2 | —— | PTC, PT100,PT1000 | PTC, PT100,PT1000 | PTC, PT100,PT1000 |
Leakage 1 | Conductance measurement | Conductance measurement, switching input | Conductance measurement, switching input | Conductance measurement |
Leakage 2 | —— | Conductance measurement, switching input | Conductance measurement, switching input | Switching input |
Anolog input | —— | —— | 0/4 – 20 mA | 0/4 – 20 mA |
Phase monitoring | Run detection | Phase sequence, phase failure, phase asymmetry, over- and undervoltage, run detection | Phase sequence, phase failure, phase asymmetry, over- and undervoltage, run detection | Phase sequence, phase failure, phase asymmetry, over- and undervoltage, run detection |
Measuring range | Phase-neutral conductor: AC 20 – 100 Hz, 60 – 277 V Phase-phase: AC 20 – 100 Hz, 60 – 480 V | Phase-phase: 3 AC 50 / 60 Hz, 100 – 690 V | Phase-phase: 3 AC 50 / 60 Hz, 100 – 690 V | Phase-phase: 3 AC 50 / 60 Hz, 100 – 690 V |
Current monitoring | —— | —— | —— | Current transformer INT185 |
Power measurement | —— | —— | —— | Apparent, active, reactive power, cos ϕ |
Relay 1 | Temperature | Alarm | Alarm | Alarm |
Relay 2 | Leakage | —— | Warning | Warning |
Interfaces | Diagnostic port (DP) | Diagnostic port (DP) | Diagnostic port (DP) | Diagnostic port (DP) Modbus RTU (RS485 |
Housing width | 22.5 mm | 45 mm | 45 mm | 45 mm |
Reset function | Reset button / external reset /mains reset | Mains reset | Mains reset | Mains reset / external reset |